OMRON Model E5ED-RX4A6M-000 E5ED-RX4D6M-000 E5ED-RX4A6M-008 E5ED-RX4D6M-008 E5ED-RX4A6M-010 E5ED-RX4D6M-010 E5ED-QX4A6M-000 E5ED-QX4D6M-000 E5ED-QX4A6M-008 E5ED-QX4D6M-008 E5ED-QX4A6M-010 E5ED-QX4D6M-

OMRONModel E5ED-RX4A6M-000 E5ED-RX4D6M-000 E5ED-RX4A6M-008 E5ED-RX4D6M-008 E5ED-RX4A6M-010 E5ED-RX4D6M-010 E5ED-QX4A6M-000 E5ED-QX4D6M-000 E5ED-QX4A6M-008 E5ED-QX4D6M-008 E5ED-QX4A6M-010 E5ED-QX4D6M-0

  • model:

OMRON

Model E5ED-RX4A6M-000 E5ED-RX4D6M-000 E5ED-RX4A6M-008 E5ED-RX4D6M-008 E5ED-RX4A6M-010 E5ED-RX4D6M-010 E5ED-QX4A6M-000 E5ED-QX4D6M-000 E5ED-QX4A6M-008 E5ED-QX4D6M-008 E5ED-QX4A6M-010 E5ED-QX4D6M-010 E5ED-CX4A6M-000 E5ED-CX4D6M-000 E5ED-CX4A6M-004 E5ED-CX4D6M-004 E5ED-CX4A6M-022 E5ED-CX4D6M-022 E5ED-RR4A6M-000 E5ED-RR4A6M-008 E5ED-QR4A6M-000 E5ED-QR4A6M-008  Model E5ED-RX4ABM-000 E5ED-RX4DBM-000 E5ED-RX4ABM-008 E5ED-RX4DBM-008 E5ED-RX4ABM-010 E5ED-RX4DBM-010 E5ED-QX4ABM-000 E5ED-QX4DBM-000 E5ED-QX4ABM-008 E5ED-QX4DBM-008 E5ED-QX4ABM-010 E5ED-QX4DBM-010 E5ED-CX4ABM-000 E5ED-CX4DBM-000 E5ED-CX4ABM-004 E5ED-CX4DBM-004 E5ED-CX4ABM-022 E5ED-CX4DBM-022 E5ED-RR4ABM-000 E5ED-RR4ABM-008 E5ED-QR4ABM-000 E5ED-QR4ABM-008

Digital Temperature Controller (48 x 96 mm)



Specifications:

Power supply voltage

A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC

Operating voltage range

85% to 110% of rated supply voltage

Power consumption

Models with option selection of 000: 6.6 VA max. at 100 to 240 VAC,
and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
All other models: 8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at
24 VAC or 3.2 W max. at 24 VDC

Sensor input

Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C,
115 to 165°C, or 140 to 260°C
Analog input
Current input:4 to 20 mA or 0 to 20 mA
Voltage input:1 to 5 V, 0 to 5 V, or 0 to 10 V

Input impedance

Current input: 150 Ω max., Voltage input: 1 MΩ min.
(Use a 1:1 connection when connecting the ES2-HB-N/THB-N.)

Control method

ON/OFF control or 2-PID control (with auto-tuning)

Control
output

Relay output

SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,
minimum applicable load: 5 V, 10 mA (reference value)

Voltage output
(for driving SSR)

Output voltage: 12 VDC ±20% (PNP), max. load current: 40 mA,
with short-circuit protection circuit
(The maximum load current is 21 mA for models with two control outputs.)

Linear current
output

4 to 20 or 0 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000

Auxiliary
output

Number of outputs

4

Output
specifications

SPST-NO relay outputs, 250 VAC, 2 A (resistive load)
Electrical life: 100,000 operations,
Minimum applicable load: 10 mA at 5 V (reference values)

Event
input

Number of inputs

2 or 4 (depends on model)

External contact
input
specifications

Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.

Non-contact input: ON: Residual voltage: 1.5 V max.,
OFF: Leakage current: 0.1 mA max.

Current flow: Approx. 7 mA per contact

Transfer
Output

Number of outputs

1 (depends on model): Transfer output type

Output
specifications

Current output: 4 to 20 mA DC, Load: 500 Ω, Resolution: Approx. 10,000
Linear voltage output: 1 to 5 V DC, Load: 1 kΩ min., Resolution: Approx. 10,000

Setting method

Digital setting using front panel keys

Indication method

11-segment digital display, individual indicators, and bar display
Character height: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm
Three displays Contents: PV/SV/MV, PV/SV/Multi-SP, PV/SV/Remaining
soak time, etc.
Numbers of digits: 4 digits each for PV, SV, and MV displays

Multi SP

Up to eight set points (SP0 to SP7) can be saved and selected using
the event inputs, key operations, or serial communications.

Bank switching

None

Other functions

Adaptive control, automatic filter adjustment, water-cooling output adjustment,
indication data (power ON time monitor, ambient temperature monitor, and
control output ON/OFF count monitors), parameter masking, operation afte
power ON, manual output, heating/cooling control, loop burnout alarm,
SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure
(HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust tuning,
PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, logic operations,temperature status display, simple
programming, moving average of input value, and display brightness setting

Ambient operating
temperature

-10 to 55°C (with no condensation or icing),
For 3-year warranty: -10 to 50°C with standard mounting
(with no condensation or icing)

Ambient operating
humidity

25% to 85%

Storage temperature

-25 to 65°C (with no condensation or icing)

Altitude

2,000 m max.

Recommended fuse

T2A, 250 VAC, time-lag, low-breaking capacity

Installation environment

Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)