Pipe |
Fluid condition | Gas |
Applicable pipe diameter | Nominal diameter 50mm~5000mm (*1) |
Spool piece | Pipe diameter | 50mm~500mm (*2) |
Flange | JIS10k standard (*3) |
Material | SGP、SUS304 --- (*4) |
Socket | Standard type | Screw type Flange type (Screw type with sensor) Flange type (Large senor type) |
Sensor |
Installation requirement | Upper stream side 15D,Lower stream side 5D or more (D is inner diameter) |
Sensor probe | Gas・・・Standard (screw type) | nominal diameter 50mm~500mm(*5) temperature -30℃~180 ℃ pressure -0.05Pa~1MPa (-0.5 ~10kgf/cm ) |
Large(flange type) | nominal diameter 500mm~(*5) temperature -30℃~180 ℃ pressure -0.05Pa~1MPa (-0.5 ~10kgf/cm ) |
Seal | Probe fittings | Combine with gas seal unit |
Gas seal unit | standard, large, custom |
Gas seal adaptor | instead of gas seal unit (not used) |
Cable | Distance from sensor probe to converter, 6m or 10m (standard) |
Converter |
General | Measurement method | Ultrasonic transit time method |
Chordal path | 1 path or 2 path (option) |
Traverse | Z or V |
Measurement compensation range | temperature +/-25℃, pressure +/- 30% |
Accuracy | ± 1.0% FS (flow velocity 5 ~ 60m/s) |
Reproducibility | ±0.2% |
Flow velocity resolution | less than 0.5mm/s |
Averaging | Default 10 sec (0 ~ 180 sec variable) |
Ultrasonic thermometer | Measure temperature (in case of air) by ultrasound transit time |
Ambient temperature | -10~+50℃ |
Power supply | Power supply | AC100V±10%, 50/60Hz, AC115V, 220V (option) |
Surge protection | Built-in surge absorber |
Power dissipation | Max.25(W) |
Output | Analog output1 | Various flow output,DC4~20mA, isolated Over range: DC0~24mA Load resistance: Less than 1000Ω |
Analog output2 | Various flow output,reverse flow, temperature, pressure Range: DC4~20mA,isolated Over range: DC0~24mA Load resistance: Less than 1000Ω |
Pulse output1 | Integrated pulse Open collector standard 30V, 0.2A Pulse width: 1.6ms or 50ms |
Pulse output2 | AIntegrate pulse, alarm, normal and reverse flow, upper l and lower limit Open collector standard 30V, 0.2A |
Pulse output3 | Alarm, normal and reverse flow, upper l and lower limit Open collector standard 30V, 0.2A |
Pulse output4 | Alarm, normal and reverse flow, upper l and lower limit Open collector standard 30V, 0.25A |
Power supply for pressure and temperature | DC24V+/-0.5V 0.2A |
Digital output | RS422×1 RS232C×1 |
Input | temperature | DC4~20mA |
Pressure | DC4~20mA |
Display | LCD | 128 x 240 dots LED back right |
Character | Alphanumeric, mathematical symbol (ex, +, -, Σ) |
Display contents | Measurement display Instantaneous flow rate (analog1,2)、 Integrated count (analog1,2) Max flow rate (analog1,2)、 Input temperature, pressure, ultrasonic temperature meter It can display content of 4 in all contents. |
Configuration view | diameter, temperature, pressure, flow range |
Adjustment view | zero point adjusting, change of time constant, low-cut |