RKC H-PCP-J Modular Controller (Process/Temperature Controller) SR Mini HG SYSTEM

RKCH-PCP-JModular Controller (Process/Temperature Controller)SR Mini HG SYSTEMSpecifications:H-PCP-J module· Basic functionData management function: Operation data, System dataUnit diagnosis fun

  • model:

RKC

H-PCP-J

Modular Controller (Process/Temperature Controller)

SR Mini HG SYSTEM


Specifications:

H-PCP-J module

·      Basic function
Data management function: Operation data, System data
Unit diagnosis function: Configuration check of function modules

·      Digital output
Number of outputs: 8 points
Output type: Temperature alarms 1 and 2 (ALM1, 2), Heater break alarm, Burnout alarm
Analog inputs 1 and 2 alarm (AI), Temperature inputs 1 and 2 (TI) alarm,
Loop break alarm, Temperature rise completion, FAIL. (configurable)
Output method: Open collector output (sink type)

·      Communication
Interface: RS-422A / RS-485 / RS-232C
Protocol:
1) ANSI X3.28 (1976)2.5 B1
2) MODBUS
3) PLC commands (MAPMAN)
PLC commands are supported only on COM.port 1 and 2. Protocol is configurable among 1), 2) and 3).

<General Specification>

·      Power supply voltage (Rating): 100 to 120Vac / 200 to 240Vac/ 24Vdc

·      Allowable ambient temperature: 0 to 50°C

·      Weight: approx.300g

·      Safety standard:

UL  UL61010-1
cUL
 CAN/CSA-22.2 NO.61010-1
CE Marking:
 Low Voltage Directive (LVD) EN61010-1  EMC Directive EN61326-1
RCM
 EN55011

H-DO-G Module

·      Number of output: 16 points

·      Output method: Open collector output (sink type)

·      Functions: Master ch: Control output from (TIO module)
Output limit function
Output ratio function
Control output cycle time: 1 to 100 sec.

H-SIO-A module

·      Input
Number of input: 1 point
Input type: 1) Voltage pulse input: High level voltage: 7 to 15Vdc, Low level voltage: 0 to 2Vdc
2) Open collector output
Sensor power supply: 12Vdc ±10%, 70mA or less

·      Control method: 1) Open loop control
2) Closed loop control (Brilliant PID control with Autotuning)
PI control available

·      Control computation cycle: 0.1 sec.

·      Control output: 1) DC voltage output: 0 to 1V, 0 to 5V, 0 to 10V,1 to 5V dc
2) DC current output: 0 to 20mA, 4 to 20mA dc

·      Alarm function (2 points): Process alarm, Deviation alarm, SV alarm

·      Alarm output (1 point): Relay contact output, 1a contact

·      External contact input (2 points) : Control ON/OFF, RUN/STOP

·      Allowable ambient temperature: 0 to 50°C

·      Weight: approx.120g