RKC COM-ME Ethernet Communication Converter
RKCCOM-MEEthernet Communication ConverterCOM-ME-1(MODBUS/TCP)· MODBUS/TCP communicationPhysical layer :100BASE-TXUser layer :MODBUS/TCPPort spec :RJ-45 x 2 portIP Address :0.0.0.0~255.255.255
- model:
RKCCOM-MEEthernet Communication ConverterCOM-ME-1(MODBUS/TCP)· MODBUS/TCP communicationPhysical layer :100BASE-TXUser layer :MODBUS/TCPPort spec :RJ-45 x 2 portIP Address :0.0.0.0~255.255.255
RKC
COM-ME
Ethernet Communication Converter
COM-ME-1(MODBUS/TCP)
· MODBUS/TCP communication
Physical layer :100BASE-TX
User layer :MODBUS/TCP
Port spec :RJ-45 x 2 port
IP Address :0.0.0.0~255.255.255.255
*Local backloop address (127.0.0.1~127.255.255.254)can not be used.
Subnet mask :0.0.0.0~255.255.255.255
· Host communication or Controller communication
SRZ: Host communication
FZ100 / FZ400 / FZ900, GZ400 / GZ900: Controller communication
Interface: RS-485
Communication speed: 9600 bps, 19200 bps, 38400 bps, 57600 bps
Protocol:
1) ANSI X3.28-1976 subcategories 2.5 and B1
2) MODBUS-RTU
Maximum connections:
SRZ: Maximum 30 modules in a combination of
Z-TIO + Z-DIO + Z-CT; the module number of
Z-DIO and Z-CT varies depending on the
total number of Z-TIO modules
(maximum 16 Z-TIO modules per connection).
FZ100 / FZ400 / FZ900, GZ400 / GZ900: Maximum 31 units.
· Loader communication
Communication speed: 38400 bps
Maximum connections: 1 unit
Connection with a loader communication cable for our USB converter COM-KG(sold separately).
· General Specification
Power supply voltage : 24V DC
Allowable ambient temperature: -10 to +55°C
Weight : Approx. 150 g
Safety standards:
1) UL : UL61010-1
2) cUL : CAN/CSA-22.2 NO.61010-1
3)CE Marking:
EMC Directive : EN61326-1
RoHS Directive : EN IEC 63000
4) RCM : EN55011