RKC
PZ400 / PZ900
Program Controller (Temperature Controller)
Specifications:
· Number of Inputs : 1 point
Input type (Universal input) : ※See the Input Range Code for the input range.
1) Temperature, DC current, DC voltage (low) input group
Thermocouple: K, J, R, S, B, E, N, T, W5Re/W26Re, PLII, PR40-20, U, L
RTD: Pt100 or JPt100 (3-wire type)
DC voltage (low): 0 to 10mVDC, 0 to 100mVdc
2) DC voltage input (high) group
0 to 1V, 0 to 5V, 1 to 5V, 0 to 10V, -5 to +5V, -10 to +10V
3) DC current input group
0 to 20mA dc, 4 to 20mA dc
· Sampling time: 0.05 sec.
· Measurement accuracy : ±(0.1% of displayed value+1 digit) ※Depends on the input and the
· Program control function
1) Number of program patterns: Max. 16 patterns
2) Number of program segments : Max.16 segments ※Up to 256 segments using Pattern link function
3) Segment time: 0 hour 0 min. to 199 hours 59 min. or 0 min.0 sec. to 199 min.59 sec. ※Continuous time setting possible
4) Optional functions: Remaining time display (Segment remaining time/Pattern remaining time)
· Time signal (4 points) DO1 to 4 (DO2 to 4 are optional) : To be specified in DO assignment
· Output 1 (OUT1) ※Control, Temperature alarm, HBA (Heater Break Alarm), LBA (Control loop break alarm), or analog retransmission can be assigned.
1) Relay contact output: 1c contact ※Highly durable relay
2) Voltage pulse for SSR driving: 0/12V dc
4) Current output: 0 to 20mA, 4 to 20mA dc
5) DC continuous voltage output: 0 to 5V, 1 to 5V, 0 to 10V
6) Transistor output: Allowable load current 100 mA
· Event function (4 points) : Assignable to OUT1 to 3, DO 1 to4
· Analog retransmission function: Analog retransmission (1 point): Assignable to OUT1 to 3.
· Loader communication : Interface RS-232C
<Specification of Options>
· Output 2 (OUT2) ※Control, Event, HBA (Heater Break Alarm), LBA (Control loop break alarm) or analog retransmission can be assigned
1) Relay contact output (a): FZ100 1a contact ※Highly durable relay
2) Voltage pulse output for SSR driving: 0/12V dc
3) Current output: 0 to 20mA, 4 to 20mA dc
4) Continuous voltage output: 0 to 5V, 1 to 5V, 0 to 10V dc
5) Transistor output: Permissible load current 100 mA
· Output 3 (OUT3) ※Universal output
※Control, Event, HBA (Heater Break Alarm), LBA (Control loop break alarm) or analog retransmission can be assigned.
1) Voltage pulse output for SSR driving: 0/14V dc
2) DC current output: 0 to 20mA, Current output : 0 to 20mA, 4 to 20mA dc
· Digital output (DO: max.4 points)
DO1 to 4: Relay contact output, 1a contact ※DO1 is supplied as standard.
· Event input (Max.6 points) : RUN, RESET, Program pattern No. switching, Dir/Rev switching, HOLD/HOLD release, STEP, AT ON/OFF, Set data lock/unlock, Interlock release, Peak/Bottom hold release
· CT input for Heater break alarm: Max.2 points
· Feedback resistance (FBR), Input: 100 to 10kΩ (standard:135Ω)
· Communication: RS-422A / RS-485