OMRON S8VK-S Power Supplies (30/60/120/240/480-W)

Brand: OMRONModel: S8VK-SProduct Name: Power Supplies (30/60/120/240/480-W)Specification:Power rating30 W60 W120 WOutput voltagec (DC)24 V24 V24 VEfficiency115 VAC input *187% typ.87% typ.90% typ.230

  • model: S8VK-S

Brand: OMRON

Model: S8VK-S

Product Name: Power Supplies (30/60/120/240/480-W)


Specification:

Power rating

30 W

60 W

120 W

Output voltagec (DC)

24 V

24 V

24 V

Efficiency

115 VAC input *1

87% typ.

87% typ.

90% typ.

230 VAC input *1

86% typ.

89% typ.

92% typ.

Input

Voltage range *2

Single-phase, 85 to 264 VAC, 90 to 350 VDC *12,
265 to 300 VAC (1 second)

Frequency *2

50/60 Hz (47 to 450 Hz)

50/60 Hz (47 to 63
Hz)

Input current

115 VAC input *1

0.58A typ.

1.1 A typ.

1.2 A typ.

230 VAC input *1

0.36A typ.

0.66 A typ.

0.63 A typ.

Power factor *1

---

0.9 min.

Leakage
current *3

115 VAC input

0.5 mA max.

230 VAC input

1 mA max.

Inrush current
*4 (for a cold
start at 25°C)

115 VAC input

16 A typ.

230 VAC input

32 A typ.

Output

Rated output current

1.3 A

2.5 A

5 A

Rated output electric power

31.2 W

60 W

120 W

Maximum boost current

1.56 A

3 A

6 A

Voltage adjustment range *5

21.6 to 28 V (with V.DJ)

Ripple & Noise
voltage *6

100 to 240 VAC
input *1

190 mVp-p max. at
20 MHz of bandwidth

190 mVp-p max. at
20 MHz of bandwidth

110 mVp-p max. at
20 MHz of bandwidth

Input variation influence *7

0.5% max.

Load variation influence *8

1.5% max.

Temperature
variation
influence

115 to 230 VAC
input

0.05%/°C max.

Start up time
*4

115 VAC input *1

1000 ms max.

1000 ms max.

1000 ms max.

230 VAC input *1

1000 ms max.

1000 ms max.

1000 ms max.

Hold time *6

115 VAC input *1

30 ms typ.

20 ms typ.

45 ms typ.

230 VAC input *1

140 ms typ.

95 ms typ.

45 ms typ.

Additional
functions

Overload protection

Yes, automatic reset

Overvoltage protection *9

Yes, 130% or higher of rated output voltage, power shut off (shut
off the input voltage and turn on the input again)

Series operation

Yes (For up to two Power Supplies, external diodes are required.)

Parallel operation

Yes (For up to two Power Supplies), Refer to Parallel Operation on
catalog for details.

Output indicator

Yes (LED: Green)

Low-voltage detection output

No

Insulation

Withstand voltage

3.0 kVAC for 1 min. (between all input terminals and output
terminals), current cutoff 10 mA

2.0 kVAC for 1 min. (between all input terminals and PE terminals),
current cutoff 10 mA

1.0 kVAC for 1 min. (between all output terminals and PE terminals),
current cutoff 20 mA

Insulation resistance

100 MΩ min. (between all output terminals and all input terminals/
PE terminals) at 500 VDC

Environ-
ment

Ambient operating temperature
*10

-40 to 70°C (Derating is required according to the temperature.
Refer to Engineering Data) (with no condensation or icing)

Storage temperature

-40 to 85°C (with no condensation or icing)

Ambient operating humidity

95% RH max. (Storage humidity: 95% RH max.)

Vibration resistance

10 to 55 Hz, maximum 5G, 0.42 mm half amplitude for 2 h each in
X, Y, and Z directions

Shock resistance

150 m/s2, 3 times each in ±X, ±Y, ±Z directions

Reliability

MTBF

135,000 hrs min. (Refer to Data Sheet Reference Value)

Life expectancy *11

10 years min.

Con-
struction

Weight

250 g max.

250 g max.

400 g max.

Cooling fan

No

Degree of protection

IP20 by EN/IEC 60529

Standards

Harmonic current emissions

Conforms to EN 61000-3-2

EMI

Conducted
Emissions

Conforms to EN 61204-3 Class B, EN 55011 Class B

Radiated
Emissions

Conforms to EN 61204-3 Class B, EN 55011 Class B

EMS

Conforms to EN 61204-3 high severity levels

Safety standards

UL Listing: UL 508 (For 30 W and 60 W only Class2 Output: Per UL 1310)
cUL: CSA C22.2 No107.1 (For 30 W and 60 W only Class2 Output: Per CSA C22.2 No.223)
UL UR: UL 62368-1 (Recognition) OVCII (≤ 3000 m) Pol2
cUR: CSA C22.2 No. 62368-1 OVCII (≤ 3000 m) Pol2
EN: EN 62477-1 OVCIII (≤ 2000 m) OVCII (2000 m≤ and≤3000) Pol2,
EN 62368-1 OVCII (≤ 3000 m) Pol2
RCM (EN61000-6-4)
PELV (EN/IEC 60204-1) *12
EN/IEC 61558-2-16:2009+A1:2013 *12
BIS: IS 13252 (Part1) *12

Marine Standards *12

Lloyd’s register (Except 30 W)

SEMI

Conforms to F47-0706 (200 to 240 VAC input)

Power rating

240 W

480 W

Output voltagec (DC)

24 V

24 V

Efficiency

115 VAC input *1

91% typ.

91% typ.

230 VAC input *1

93% typ.

93% typ.

Input

Voltage range *2

Single-phase, 85 to 264 VAC, 90 to 350 VDC *12, 265 to 300 VAC
(1 second)

Frequency *2

50/60 Hz (47 to 63 Hz)

Input current

115 VAC input *1

2.4 A typ.

4.6 A typ.

230 VAC input *1

1.3 A typ.

2.3 A typ.

Power factor *1

0.9 min.

0.9 min.

Leakage
current *3

115 VAC input

0.5 mA max.

230 VAC input

1 mA max.

Inrush current
*4 (for a cold
start at 25°C)

115 VAC input

16 A typ.

230 VAC input

32 A typ.

Output

Rated output current

10 A

20 A

Rated output electric power

240 W

480 W

Maximum boost current

15 A

30 A

Voltage adjustment range *5

21.6 to 28 V (with V.ADJ)

Ripple & Noise
voltage *6

100 to 240 VAC
input *1

100 mVp-p max.
at 20 MHz of bandwidth

130 mVp-p max.
at 20 MHz of bandwidth

Input variation influence *7

0.5% max.

Load variation influence *8

1.5% max.

Temperature
variation
influence

115 to 230 VAC
input

0.05%/°C max.

Start up time
*4

115 VAC input *1

1000 ms max.

1000 ms max.

230 VAC input *1

1000 ms max.

1000 ms max.

Hold time *6

115 VAC input *1

35 ms typ.

30 ms typ.

230 VAC input *1

35 ms typ.

30 ms typ.

Additional
functions

Overload protection

Yes, automatic reset

Overvoltage protection *9

Yes, 130% or higher of rated output voltage, power shut off (shut
off the input voltage and turn on the input again)

Series operation

Yes (For up to two Power Supplies, external diodes are required.)

Parallel operation

Yes (For up to two Power Supplies), Refer to Parallel Operation on
catalog for details.

Output indicator

Yes (LED: Green)

Low-voltage detection output

Yes (Photoswitch output: 30 VDC max., 50 mA max.)

Insulation

Withstand voltage

3.0 kVAC for 1 min. (between all input terminals and output
terminals), current cutoff 20 mA

2.0 kVAC for 1 min. (between all input terminals and PE terminals),
current cutoff 20 mA

1.0 kVAC for 1 min. (between all output terminals and PE terminals),
current cutoff 20 mA

500 VAC for 1 min (between all output terminals and all low-voltage
detection output terminals), current cutoff 10 mA

Insulation resistance

100 MΩ min. (between all output terminals/all low-voltage
detection output terminals and all input terminals/PE terminals) at
500 VDC

Environ-
ment

Ambient operating temperature
*10

-40 to 70°C (Derating is required according to the temperature.
Refer to Engineering Data) (with no condensation or icing)

Storage temperature

-40 to 85°C (with no condensation or icing)

Ambient operating humidity

95% RH max. (Storage humidity: 95% RH max.)

Vibration resistance

10 to 55 Hz, maximum 5G, 0.42 mm half amplitude for 2 h each in
X, Y, and Z directions

Shock resistance

150 m/s2, 3 times each in ±X, ±Y, ±Z directions

Reliability

MTBF

135,000 hrs min. (Refer to Data Sheet Reference Value)

Life expectancy *11

10 years min.

Con-
struction

Weight

700 g max.

1150 g max.

Cooling fan

No

Degree of protection

IP20 by EN/IEC 60529

Standards

Harmonic current emissions

Conforms to EN 61000-3-2

EMI

Conducted
Emissions

Conforms to EN 61204-3 Class B, EN 55011 Class B

Radiated
Emissions

Conforms to EN 61204-3 Class B, EN 55011 Class B

EMS

Conforms to EN 61204-3 high severity levels

Safety standards

UL Listing: UL 508
cUL: CSA C22.2 No107.1
UL UR: UL 62368-1 (Recognition) OVCII (≤ 3000 m) Pol2
cUR: CSA C22.2 No.62368-1 OVCII (≤ 3000 m) Pol2
EN: EN 62477-1 OVCIII (≤ 2000 m) OVCII (2000 m≤ and≤3000) Pol2,
EN 62368-1 OVCII (≤ 3000 m) Pol2
PELV (EN/IEC 60204-1) *12
EN/IEC 61558-2-16:2009+A1:2013 *12
BIS: IS 13252 (Part1) *12

Marine Standards *12

Lloyd's register

SEMI

Conforms to F47-0706 (200 to 240 VAC input)












首页