Power rating | 30 W | 60 W | 120 W |
Output voltagec (DC) | 24 V | 24 V | 24 V |
Efficiency | 115 VAC input *1 | 87% typ. | 87% typ. | 90% typ. |
230 VAC input *1 | 86% typ. | 89% typ. | 92% typ. |
Input | Voltage range *2 | Single-phase, 85 to 264 VAC, 90 to 350 VDC *12, 265 to 300 VAC (1 second) |
Frequency *2 | 50/60 Hz (47 to 450 Hz) | 50/60 Hz (47 to 63 Hz) |
Input current | 115 VAC input *1 | 0.58A typ. | 1.1 A typ. | 1.2 A typ. |
230 VAC input *1 | 0.36A typ. | 0.66 A typ. | 0.63 A typ. |
Power factor *1 | --- | 0.9 min. |
Leakage current *3 | 115 VAC input | 0.5 mA max. |
230 VAC input | 1 mA max. |
Inrush current *4 (for a cold start at 25°C) | 115 VAC input | 16 A typ. |
230 VAC input | 32 A typ. |
Output | Rated output current | 1.3 A | 2.5 A | 5 A |
Rated output electric power | 31.2 W | 60 W | 120 W |
Maximum boost current | 1.56 A | 3 A | 6 A |
Voltage adjustment range *5 | 21.6 to 28 V (with V.DJ) |
Ripple & Noise voltage *6 | 100 to 240 VAC input *1 | 190 mVp-p max. at 20 MHz of bandwidth | 190 mVp-p max. at 20 MHz of bandwidth | 110 mVp-p max. at 20 MHz of bandwidth |
Input variation influence *7 | 0.5% max. |
Load variation influence *8 | 1.5% max. |
Temperature variation influence | 115 to 230 VAC input | 0.05%/°C max. |
Start up time *4 | 115 VAC input *1 | 1000 ms max. | 1000 ms max. | 1000 ms max. |
230 VAC input *1 | 1000 ms max. | 1000 ms max. | 1000 ms max. |
Hold time *6 | 115 VAC input *1 | 30 ms typ. | 20 ms typ. | 45 ms typ. |
230 VAC input *1 | 140 ms typ. | 95 ms typ. | 45 ms typ. |
Additional functions | Overload protection | Yes, automatic reset |
Overvoltage protection *9 | Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
Series operation | Yes (For up to two Power Supplies, external diodes are required.) |
Parallel operation | Yes (For up to two Power Supplies), Refer to Parallel Operation on catalog for details. |
Output indicator | Yes (LED: Green) |
Low-voltage detection output | No |
Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals and output terminals), current cutoff 10 mA |
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 10 mA |
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 20 mA |
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/ PE terminals) at 500 VDC |
Environ- ment | Ambient operating temperature *10 | -40 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing) |
Storage temperature | -40 to 85°C (with no condensation or icing) |
Ambient operating humidity | 95% RH max. (Storage humidity: 95% RH max.) |
Vibration resistance | 10 to 55 Hz, maximum 5G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions |
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions |
Reliability | MTBF | 135,000 hrs min. (Refer to Data Sheet Reference Value) |
Life expectancy *11 | 10 years min. |
Con- struction | Weight | 250 g max. | 250 g max. | 400 g max. |
Cooling fan | No |
Degree of protection | IP20 by EN/IEC 60529 |
Standards | Harmonic current emissions | Conforms to EN 61000-3-2 |
EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
EMS | Conforms to EN 61204-3 high severity levels |
Safety standards | UL Listing: UL 508 (For 30 W and 60 W only Class2 Output: Per UL 1310) cUL: CSA C22.2 No107.1 (For 30 W and 60 W only Class2 Output: Per CSA C22.2 No.223) UL UR: UL 62368-1 (Recognition) OVCII (≤ 3000 m) Pol2 cUR: CSA C22.2 No. 62368-1 OVCII (≤ 3000 m) Pol2 EN: EN 62477-1 OVCIII (≤ 2000 m) OVCII (2000 m≤ and≤3000) Pol2, EN 62368-1 OVCII (≤ 3000 m) Pol2 RCM (EN61000-6-4) PELV (EN/IEC 60204-1) *12 EN/IEC 61558-2-16:2009+A1:2013 *12 BIS: IS 13252 (Part1) *12 |
Marine Standards *12 | Lloyd’s register (Except 30 W) |
SEMI | Conforms to F47-0706 (200 to 240 VAC input) |
Power rating | 240 W | 480 W |
Output voltagec (DC) | 24 V | 24 V |
Efficiency | 115 VAC input *1 | 91% typ. | 91% typ. |
230 VAC input *1 | 93% typ. | 93% typ. |
Input | Voltage range *2 | Single-phase, 85 to 264 VAC, 90 to 350 VDC *12, 265 to 300 VAC (1 second) |
Frequency *2 | 50/60 Hz (47 to 63 Hz) |
Input current | 115 VAC input *1 | 2.4 A typ. | 4.6 A typ. |
230 VAC input *1 | 1.3 A typ. | 2.3 A typ. |
Power factor *1 | 0.9 min. | 0.9 min. |
Leakage current *3 | 115 VAC input | 0.5 mA max. |
230 VAC input | 1 mA max. |
Inrush current *4 (for a cold start at 25°C) | 115 VAC input | 16 A typ. |
230 VAC input | 32 A typ. |
Output | Rated output current | 10 A | 20 A |
Rated output electric power | 240 W | 480 W |
Maximum boost current | 15 A | 30 A |
Voltage adjustment range *5 | 21.6 to 28 V (with V.ADJ) |
Ripple & Noise voltage *6 | 100 to 240 VAC input *1 | 100 mVp-p max. at 20 MHz of bandwidth | 130 mVp-p max. at 20 MHz of bandwidth |
Input variation influence *7 | 0.5% max. |
Load variation influence *8 | 1.5% max. |
Temperature variation influence | 115 to 230 VAC input | 0.05%/°C max. |
Start up time *4 | 115 VAC input *1 | 1000 ms max. | 1000 ms max. |
230 VAC input *1 | 1000 ms max. | 1000 ms max. |
Hold time *6 | 115 VAC input *1 | 35 ms typ. | 30 ms typ. |
230 VAC input *1 | 35 ms typ. | 30 ms typ. |
Additional functions | Overload protection | Yes, automatic reset |
Overvoltage protection *9 | Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
Series operation | Yes (For up to two Power Supplies, external diodes are required.) |
Parallel operation | Yes (For up to two Power Supplies), Refer to Parallel Operation on catalog for details. |
Output indicator | Yes (LED: Green) |
Low-voltage detection output | Yes (Photoswitch output: 30 VDC max., 50 mA max.) |
Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals and output terminals), current cutoff 20 mA |
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA |
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 20 mA |
500 VAC for 1 min (between all output terminals and all low-voltage detection output terminals), current cutoff 10 mA |
Insulation resistance | 100 MΩ min. (between all output terminals/all low-voltage detection output terminals and all input terminals/PE terminals) at 500 VDC |
Environ- ment | Ambient operating temperature *10 | -40 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing) |
Storage temperature | -40 to 85°C (with no condensation or icing) |
Ambient operating humidity | 95% RH max. (Storage humidity: 95% RH max.) |
Vibration resistance | 10 to 55 Hz, maximum 5G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions |
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions |
Reliability | MTBF | 135,000 hrs min. (Refer to Data Sheet Reference Value) |
Life expectancy *11 | 10 years min. |
Con- struction | Weight | 700 g max. | 1150 g max. |
Cooling fan | No |
Degree of protection | IP20 by EN/IEC 60529 |
Standards | Harmonic current emissions | Conforms to EN 61000-3-2 |
EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
EMS | Conforms to EN 61204-3 high severity levels |
Safety standards | UL Listing: UL 508 cUL: CSA C22.2 No107.1 UL UR: UL 62368-1 (Recognition) OVCII (≤ 3000 m) Pol2 cUR: CSA C22.2 No.62368-1 OVCII (≤ 3000 m) Pol2 EN: EN 62477-1 OVCIII (≤ 2000 m) OVCII (2000 m≤ and≤3000) Pol2, EN 62368-1 OVCII (≤ 3000 m) Pol2 PELV (EN/IEC 60204-1) *12 EN/IEC 61558-2-16:2009+A1:2013 *12 BIS: IS 13252 (Part1) *12 |
Marine Standards *12 | Lloyd's register |
SEMI | Conforms to F47-0706 (200 to 240 VAC input) |
|
|
|
|
|
|
|
|
|
|