OMRON S8FS-G Switch Mode Power Supply (15/30/50/100/150/300/600-W)

Brand: OMRONModel: S8FS-GProduct Name: Switch Mode Power Supply (15/30/50/100/150/300/600-W)Specification: Power rating15 WOutput voltage (VDC)5 V12 V15 V24 VEfficiency *1100 VAC input80% typ.84% typ.

  • model: S8FS-G

Brand: OMRON

Model: S8FS-G

Product Name: Switch Mode Power Supply (15/30/50/100/150/300/600-W)


Specification:

Power rating

15 W

Output voltage (VDC)

5 V

12 V

15 V

24 V

Efficiency *1

100 VAC input

80% typ.

84% typ.

84% typ.

85% typ.

200 VAC input

80% typ.

84% typ.

84% typ.

86% typ.

230 VAC input

80% typ.

84% typ.

84% typ.

86% typ.

Input

Voltage range *1

Single phase, 85 to 264 VAC, 80 to 370 VDC

Frequency *1

50/60 Hz (47 to 450 Hz)

Current *1

100 VAC input

0.32 A typ.

200 VAC input

0.2 A typ.

Power factor *1

---

Leakage
current *1

100 VAC input

0.5 mA max.

200 VAC input

1 mA max.

Inrush
current *1 (for
a cold start at
25°C)

100 VAC input

14 A typ.

200 VAC input

28 A typ.

Output

Rated Output Current

3 A

1.3 A

1 A

0.65 A

Voltage adjustment range *1

-10% to 15% (with V.ADJ)

Ripple & Noise
voltage *1

100 to 240
VAC input

40 mVp-p max.

40 mVp-p max.

40 mVp-p max.

60 mVp-p max.

Input variation influence *1

0.5% max.

Load variation influence *1

1.0% max.

Temperature
variation
influence

100 to 240
VAC input

0.05%/°C max.

Startup time *1

100 VAC input

1,000 ms max.

200 VAC input

1,000 ms max.

Hold time *1

100 VAC input

15 ms typ.

14 ms typ.

15 ms typ.

15 ms typ.

200 VAC input

75 ms typ.

70 ms typ.

75 ms typ.

70 ms typ.

Additional
functions

Overload protection

Yes, automatic reset

Overvoltage protection *1

Yes, 120% or higher of rated output voltage, power shut off (shut off the
input voltage and turn on the input again)

Overheat protection

No

Series operation

Yes (For up to two Power Supplies, external diodes are required.)

Parallel operation

No (However, backup operation is possible, external diodes are required.)

Remote sensing

No

Remote control

No

Output indicator

Yes (LED: Green)

Insulation

Withstand voltage

3 kVAC for 1 min. (between all input terminals and output terminals)
current cutoff 20 mA

2 kVAC for 1 min. (between all input terminals and PE terminals) current
cutoff 20 mA

1 kVAC for 1 min. (between all output terminals and PE terminals)
current cutoff 20 mA

Insulation resistance

100 MΩ min. (between all output terminals and all input terminals/PE
terminals) at 500 VDC

Environ-
ment

Ambient operating
temperature

-20 to 70°C (Derating is required according to the temperature.)
(with no condensation or icing)

Storage temperature

-25 to 75°C (with no condensation or icing)

Ambient operating humidity

90% max. (Storage humidity: 90% max.)

Vibration resistance

10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y,
and Z directions

Shock resistance

150 m/s2, 3 times each in ±X, ±Y, ±Z directions

Reliability

MTBF

135,000 hrs min.

Life expectancy *1

10 years min.

Con-
struction

Dimensions (W×H×D)

Refer to Dimensions.

Weight

250 g

Cooling fan

No

Degree of protection

---

Standards

Harmonic current emissions

Conforms to EN 61000-3-2

EMI *1

Conducted
Emissions

Conforms to EN 61204-3 Class B, EN 55011 Class B

Radiated
Emissions

Conforms to EN 61204-3 Class B, EN 55011 Class B

EMS

Conforms to EN 61204-3 high severity levels

Safety Standards *2

UL 508 (Listing, excluding models with connector option)
UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2)
CSA C22.2 No.107.1 (excluding models with connector option)
CSA C22.2 No.62368-1 (excluding models with connector option)
EN 62477-1 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2)
EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2)
Conforms to EN/IEC 61558-2-16
Conforms to PELV (EN/IEC 60204-1)
RCM (EN61000-6-4)

Marine Standards

No

SEMI

Conforms to F47-0706 (200 VAC input)

* Please contact us about more specification details for 30/50/100/150/300/600-W.