Item | Specifications |
Operation power supply | Power supply voltage and frequency | K7TM-A2MA: 100 to 240 V AC, 50/60 Hz K7TM-A2MD: 24 V AC, 50/60 Hz, 24 V DC |
Operating power supply voltage range | 85% to 110% of the rated voltage |
Operating frequency range | 45 to 65 Hz |
Power consumption | K7TM-A2MA: 8.5 VA max. (100 to 240 V AC) |
K7TM-A2MD: 5.2 VA max. (24 V AC)/ 2.9 W max. (24 V DC) |
Recommend external fuse | T2A, time delay, high-breaking capacity |
Ambient operating temperature | -10 to 55°C |
Ambient operating humidity | 25% to 85% |
Storage temperature | -20 to 65°C (with no condensation or icing) |
Altitude | 2,000 m max. |
Insulation resistance | 20 mΩ min. Between all external terminals and case; Between all power supply terminals and all other terminals; Between (all voltage input terminals + all CT input terminals) and (all communications terminals + all transistor terminals); Between all voltage input terminals and all CT input terminals; Between the channels of voltage inputs; Between the channels of CT inputs |
Dielectric strength | 2,000 V AC for 1 minute Between all external terminals and case; Between all power supply terminals and all other terminals; Between (all voltage input terminals + all CT input terminals) and (all communications terminals + all transistor terminals); Between all voltage input terminals and all CT input terminals; Between the channels of voltage inputs; Between the channels of CT inputs |
Vibration resistance | Frequency 10 to 55 Hz, 0.35-mm single amplitude, acceleration 50 m/s², 10 sweeps of 5 min each in X, Y, and Z directions |
Shock resistance | 100 m/s2, 3 times each in X, Y, and Z axes, 6 directions |
Degree of protection | IP20 |
Terminal block type | Push-In Plus |
Exterior color | Black (Munsell N 1.5) |
Mounting | DIN Track |
Weight | Approx. 200 g |
Wiring material | Wire type | Solid or Stranded wire |
Wiring material | Copper |
Recommended wires | 0.25 to 1.5 mm2 AWG 24 to AWG 16 |
Stripping length (without ferrules) | 8 mm |
Installation environment | Operation voltage: EN/IEC 61010-1 Pollution Degree 2, Overvoltage category II |
Measurement circuit: EN/IEC 61010-2-030 Pollution Degree 2, CAT II 600 V or CAT III 300 V |
Industrial electromagnetic environment | EN/IEC 61326-1 Industrial electromagnetic environment |