KEYENCE
KV-NC4AD
A/D Conversion Unit 4-point type
Specifications:
Model | KV-NC4AD |
Conversion speed | 80 µs/channel*1 |
Conversion | A/D conversion |
Points | 4 (single end) |
Range/resolution | Voltage | -10 V to +10 V | 1/8000 2.5mV |
0 to 10 V | 1/4000 2.5mV |
0 to 5 V | 1/4000 1.25mV |
1 to 5 V | 1/3200 1.25mV |
Current | 0 to 20 mA | 1/4000 5µA |
4 to 20 mA | 1/3200 5µA |
Conversion precision | Voltage | Without temperature compensation | ±0.3% of F.S. (at 25°C ±5°C) ±0.5% of F.S. (at 0 to 55°C) |
With temperature compensation | ±0.3% of F.S. (at 0 to 55°C) |
Current | Without temperature compensation | ±0.4% of F.S. (at 25°C ±5°C) ±0.6% of F.S. (at 0 to 55°C) |
With temperature compensation | ±0.4% of F.S. (at 0 to 55°C) |
Input resistance | Voltage | 5MΩ |
Current | 250Ω |
Absolute maximum input | Voltage | ±15V |
Current | ±30mA |
Isolation method | Between analogue input | Isolated (photocoupler, transformer) |
Between analogue input channels | Non-isolated |
Minimum load resistance | Voltage | ― |
Maximum load resistance | Current |
Special functions | Input range switching, temperature fluctuation compensation enabling/disabling, channel skip, scaling, special data offset, peak-/bottom-hold, zero clip, zero shift, comparator, averaging (time-specified, count-specified, moving average), disconnection detection |