Model | KV-NC4TP |
|
Temperature input unit | Number of inputs | 4*1 |
|
Input | Thermocouple, Platinum resistance thermometer |
|
Input range | Thermocouple | K : -270.0 to 1372.0˚C J : -210.0 to 1200.0˚C T : -270.0 to 400.0˚C E : -270.0 to 1000.0˚C N : -270.0 to 1300.0˚C R : -50.0 to 1768.0˚C S : -50.0 to 1768.0˚C B : 0.0 to 1820.0˚C WRe5-26 : 0.0 to 2315.0˚C |
|
Platinum resistance thermometer | Pt100 : -200.0 to 850.0˚C JPt100 : -200.0 to 600.0˚C |
|
Overall accuracy | Thermocouple | ±0.2% of F.S. (at 25°C ±5°C) ±0.4% of F.S. (at 0 to 55°C) |
|
Platinum resistance thermometer |
|
Allowable wiring resistance | 100 Ω max./wire (no variation allowed among three wires) |
|
Conversion speed | 125ms/ch |
|
Isolation method | Between input terminals and base unit : Photocoupler/semiconductor relay/transformer isolation Between channels : (When resistance thermometer is not used) : Semiconductor relay isolation : When resistance thermometer is used : No isolation |
|
Special functions | Channel skip, disconnection detection, averaging (time average, count average, moving average), special data offset, peak-/bottom-hold, alarm function, abnormal input setting function |
|
Internal current consumption | 40mA or less |
|
Weight | Approx. 110 g |
|
*1 Individual setting is possible for each channel. |
|