KEYENCE
KL-2DA
D/A Conversion Unit, 2 Analog Output Channels
Specifications:
Model | KL-2DA |
General specifications | Current consumption | 190mA or less |
Vibration resistance | 10 to 55 Hz, 1.5 mm or less double amplitude for 2 hours in each of the X, Y, and Z directions |
Power voltage | 24 VDC ± 10% |
Operating ambient temperature | 0 to 60°C |
Operating ambient humidity | 35 to 85%RH |
Operating environment | Minimal amount of dust and corrosive gas present |
Withstand voltage | 1,500 VAC for 1 minute (between the batch of external input terminals, the case, and the batch of power supply terminals) |
Insulation resistance | 50 MΩ or more (between the batch of external input terminals, the case, and the batch of power supply terminals) |
Weight | approx 180g |
Performance specifications | Conversion speed | 250 µs/ch |
Total accuracy (25°C) | Voltage | 0.2% of F.S. |
Current |
Total accuracy (0 to 60°C) | Voltage | 0.4% of F.S. |
Current |
Isolation mode | Photocoupler isolation (channels are not isolated from each other) |
Noise resistance | Normal mode | 500 Vp-p, 1 µs, 50 ns (measured with a noise simulator) |
Common mode | 1,500 Vp-p (measured with a noise simulator) |
Number of analog outputs | 2 |
Output range (resolution) | Voltage | 0 to +5V (1.25mV 1/4000)+1 to +5V (1mV 1/4000)0 to +10V (2.5mV 1/4000)-10 to +10V (2.5mV 1/8000) |
Current | 0 to 20 mA (5 µA 1/4000), 4 to 20 mA (4 µA 1/4000) |
Minimum load resistance, maximum load resistance | Voltage | 1 kΩ |
Current | 400 Ω |