Model | KV-XL402*1 |
Type | Serial communication unit |
Communication standard | RS-422A / RS-485 (4 wires), RS-422A / RS-485 (2 wires) |
Connection interface | European terminal block with 5 poles(detachable) × 2 ports |
Transmission specification | Electrical termination (Terminator) | ON / OFF set by the switch on the front face |
Transmission rate | 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200, 230,400 bps |
Transmission method | RS-422A / RS-485(4 wires): Full duplex, RS-422A / RS-485(2 wires): Half-duplex |
Data format | Start bit: 1 bit Data bit: 7 or 8 bits Stop bit: 1 or 2 bits |
Error detection | Parity: Even, odd, none |
RS/CS flow control | ON or OFF(only in PLC link mode) |
Transmission distance | Total extension: 1,200 m max.*2*3 |
Number of transmission units | 32*2 |
Connectable CPU units | KV-8000/KV-7500/KV-7300 |
Refreshes | Automatic refresh, direct refresh,inter-unit synchronisation refresh |
Serial communication functions | Non-procedure, PROTOCOL STUDIO, Modbus RTU slave, etc. |
Serial communication function execution methods | Ladder program, unit program (flow) |
Unit program capacity | 3 MB (max. number of blocks: approx. 20,000) |
Flow | Maximum number of flows | 256 |
Number of simultaneous activities | Unlimited |
Internal data memory | 524,288 words |
PROTOCOL STUDIO | Transmission method | Cyclic communication: Tx + Rx, Tx only, Rx only Event communication: Tx + Rx, Tx only, Rx only, Tx + Continuous Rx, Break Tx |
Maximum number of connected devices | 2 |
Maximum number of communication commands | 48 / 96*4 |
Maximum number of total frames | Rx: 48 / 96*4 × 16; Tx: 48 / 96*4 × 1 |
Maximum number of compared and receive frames | 16 per command |
Maximum number of block elements | 96 per frame |
Transmission data length | 1 to 2,048 bytes per frame |
Received data length |
PLC link | Communication patterns | Write, read, transfer |
Number of link settings | 512 settings max.*5 |
Link data size | 1,440 words max. per setting (bit: 720 words, word: 720 words) 737,280 words max. (total)(1,440 words × 512 settings) |
Data unit | 1 word |
Number of connected models | 2 models max.(1 model × 2 ports) |
Number of connected units | 2 max.(1 unit × 2 ports) |
Trigger types | Cyclic / event (64 settings max. for event*5) |
Update interval | 10 to 65,535 ms |
Internal current consumption | 150 mA or less |
Weight | Approx. 190 g |
*1 For KV-8000/KV-7000 Series *2 Depends on the function to be used. *3 The total extension is 500 m max. at a transmission rate of 230,400 bps. The transmission rate and distance vary depending on the device to be connected. Check the values according to the actual device. *4 The max. is 48 when “Standard” is set for the number of communication commands on the Unit Editor and 96 when “Extended” is set. *5 Total for one KV-XL202 / XL402 unit. |