Model | KV-N60ATP |
General specifications | Power voltage | 100 to 240 VAC (+10%/-15%) |
Operating ambient temperature | 0 to 55°C (no freezing)*1*2 |
Operating ambient humidity | 5 to 95% RH (no condensation)*1 |
Operating environment | As little dust and corrosive gases as possible |
Noise immunity | 1500 V peak-to-peak or more, pulse width 1 µs, 50 ns (by noise simulator), IEC standard compliant (IEC61000-4-2/3/4/6) |
Withstand voltage | 1500 VAC for 1 minute, between power supply terminal and I/O terminals and between all external terminals and case |
Insulation resistance | 50 MΩ or more (500 VDC megger used to perform measurements between power terminal and input terminals, and between all external terminals and case) |
Output power supply voltage | 24 VDC (±10%; output capacity: 0.6 A) |
Storage temperature | -25 to +75°C |
Vibration resistance | Intermittent vibration | Frequency: 5 to 9 Hz | Amplitude: 3.5 mm*3*4 |
Frequency: 9 to 150 Hz | Acceleration: 9.8 m/s2*3*5 |
Continuous vibration | Frequency: 5 to 9 Hz | Amplitude: 1.75 mm*3*5 |
Frequency: 9 to 150 Hz | Acceleration: 4.9 m/s2*3*5 |
Shock resistance | Acceleration: 150 m/s2, application time: 11 ms, two times in each of the X, Y, and Z directions |
Operating altitude | 2000 m or less |
Overvoltage category | AC: II, DC: I |
Pollution degree | 2 |
Performance specifications | Calculation control method | Programme storage method |
I/O control method | Refresh method |
Programming language | Expanded ladder, KV Script, mnemonic |
Number of instructions | Basic instructions: 81 kinds and 182 instructions, Application instructions: 39 kinds and 56 instructions Calculation instructions: 123 kinds and 311 instructions, Expansion instructions: 92 kinds and 141 instructions, Total: 335 kinds and 690 instructions |
Instruction execution speed | Basic instruction: 50 ns minimum, Application instruction: 170 ns minimum |
Program capacity | 16k steps |
Maximum number of attachable I/O units | 8 |
Maximum number of I/O points | 256 (excluding the base unit I/O) |
Input relay/Output relay/Internal auxiliary relay | R | Total of 9600 points 1 bit (R000 to R59915) |
Link relay | B | 8192 points 1 bit (B0 to B1FFF) |
Internal auxiliary relay | MR | 9600 points 1 bit (MR000 to MR59915) |
Latch relay | LR | 3200 points 1 bit (LR000 to LR19915) |
Control relay | CR | 1440 points 1 bit (CR000 to CR8915) |
Timer | T | 512 points 32 bits (T0 to T511) |
Counter | C | 256 points 32 bits (C0 to C255) |
Data memory | DM | 32768 points 16 bits (DM0 to DM32767) |
Link register | W | 16384 points 16 bits (W0 to W3FFF) |
Temporary memory | TM | 512 points 16 bits (TM0 to TM511) |
High-speed counter | CTH | 4 points (CTH0 to CTH3) 32-bit automatic reset counter*6 (Input response: 100 kHz per single phase, 50 kHz per phase difference)*7 |
High-speed counter comparator | CTC | 8 points (CTC0 to CTC7) 32 bits, two points per high-speed counter |
Index register | Z | 12 points 32 bits (Z01 to Z12) |
Control memory | CM | 9000 points 16 bits (CM0 to CM8999) |
Positioning pulse output | 4 axes Maximum output frequency: 100 kHz |
Base unit I/O | Input: 36 points, output: 24 points Input common: 1 point, Output common: 8 points (R type)/3 points (T/TP type) |
Number of comments and labels that can be stored in the main unit | Device comment | 20000 When a maximum-length ladder programme is written with no labels. |
Label | 28000 When a maximum-length ladder programme is written with no device comments. |
Power off hold function | Programme memory | Flash ROM can be rewritten 10000 times |
Device | Nonvolatile RAM*8 |
Self-diagnosis function | CPU error, RAM error, and other problems |
Input specifications | Relay number | General input: R000 to R007, R100 to R203 (28 points)*9 High-speed A-phase and B-phase input: R008 to R015 (4 channels, 8 points in total) |
Input mode | 24 VDC input (open collector) |
Maximum input voltage | 26.4 VDC |
Rated input voltage | 24 VDC (General input: 5.3 mA, High-speed A-phase and B-phase input: 6.5 mA*10) |
Minimum ON voltage | 19 VDC |
Maximum OFF current | 1.5 mA |
Common method | General input: All inputs/common (1 terminal) High-speed A-phase and B-phase input: Shared common for all points (shared with general input) |
Circuit delay time | General input (below for R108 to R203): OFF to ON: Max. 50 µs (Typ. 7 µs), ON to OFF: Max. 150 µs (Typ. 70 µs) High-speed A-phase and B-phase input OFF to ON: Max. 2 µs (Typ. 1.1 µs), ON to OFF: Max. 2 µs (Typ. 0.3 µs)*11 |
Input time constant | Normal: 10 ms, When the HSP instruction is used: 10 µs When CR2305 is turned ON: 10 µs to 10 ms, eight-level switching is possible (set with CM1620). Can also be set from the Unit Editor.*11 |
Delay by input time constant Input time constant setting 10 µs: Digital filter 1.6 to 2 µs Input time constant setting 20 µs: Digital filter 9 to 12 µss Input time constant setting 110 µs: Digital filter 90 to 93 µs Input time constant setting 500 µs: Digital filter 300 to 400 µs Input time constant setting 1 ms: Digital filter 800 to 900 µs Input time constant setting 2.5 ms: Digital filter 2.3 to 2.4 ms Input time constant setting 5 ms: Digital filter 4.0 to 4.5 ms Input time constant setting 10 ms: Digital filter 9 to 9.5 ms |
Response frequency | (High-speed A-phase and B-phase input) Single phase: 100 kHz, phase difference: 50 kHz, 24 V±10%, Duty 50% |
Output specifications | Relay number | General output: R508 to R607 (16 points), High-speed output: R500 to R507 (8 points) |
Output mode | Source output type MOSFET (P-ch) output |
Rated load | 30 VDC, 0.5 A |
Maximum OFF voltage | 30 VDC |
Leakage current at OFF | 100 µA or less |
Residual voltage at ON | 0.8 VDC or less (with 0.5 A output), 0.6 VDC or less (with 0.3 A output) |
Common method | 8 to 10 points/1 common |
ON/OFF response time | General output: OFF to ON : 100 µs (load of 1 mA or more), ON to OFF : 200 µs (load of 1 mA or more) High-speed output: OFF to ON: 2 µs (7 to 100 mA load), ON to OFF: 5 µs (7 to 100 mA load) |
Overcurrent protection | Protection provided for each common*12 |
Output frequency | High-speed output: 100 kHz (7 to 100 mA load) |
Built-in serial port | Interface | Communication standard | RS-232C |
Connection | Modular connector |
Transmission specifications RS-232C | Baud rate | 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps |
Transmission method | Full duplex |
Data format | Start bit | 1 bit |
Data bits | 7 bits, 8 bits |
Stop bits | 1 bit, 2 bits |
Error detection | Parity | Even, odd, none |
Transmission distance | 15 m |
Number of transmission units | 1 |
Indication | SD (green), RD (red) |
Internal current consumption | 85 VA (VA is calculated with a power factor of 30%.) |
Weight | Approx. 750 g |
*1 The range guaranteed as a system (excluding items specially noted for the units and cassettes). *2 The temperature below the unit centre (30 mm) inside a control panel. *3 These specifications correspond to situations in which the unit is mounted on a DIN rail and in which the unit is mounted on the panel directly. *4 Conforms to JIS B 3502 and IEC61131-2, Number of scans: 10 times (100 minutes) in each of the X, Y, and Z directions *5 Conforms to JIS B 3502 and IEC61131-2. Number of scans: 10 times (100 minutes) in each of the X, Y, and Z directions *6 You can also configure the settings so that automatic reset is not used. *7 Only open collectors are supported. Line drivers are not supported. *8 You can set the target device by clicking "CPU system setting" and then "Power off holding" in KV STUDIO. *9 The response time increases for R108 to R203. *10 Reference value of input current. *11 The input response time corresponding to the input time constant can be calculated as shown below. (Response time) = (Circuit delay of the input circuit) + (Delay by the digital filter) Example: Maximum response time when the input time constant is set to 500 µs OFF to ON: 30 µs (circuit delay) + 400 µs (digital filter) = 430 µs, ON to OFF: 50 µs (circuit delay) + 400 µs (digital filter) = 450 µs *12 If an overcurrent occurs, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common until the cause of the problem is removed. |