Model | MS2-H150 |
Input conditions | Input voltage | 85 to 264 VAC, 110 to 370 VDC*1 |
Frequency | 47 to 63 Hz, DC*1 |
Inputconditions | Input current (100/200 VAC) | 2.2/1.1A or less |
Efficiency (100/200 VAC) | 82/85% typ. (with 100% load) |
Leakage current (100/200 VAC) | 0.4/0.75 mA max. (with 100% load) |
Rush current (100/200 VAC) | 25/50 A max. (with 100% load, at 25°C cold start) |
Output characteristics | Rated voltage | 24V |
Variable voltage range | ±5% (with V.ADJ) |
Rated current | 6.5A |
Ripple/noise voltage | 180mV (p-p) or less |
Input fluctuation | 0.4% or less |
Load fluctuation | 1.5% or less |
Temperature fluctuation | 0.02 %/ ºC max. |
Startup time | 500 ms max. (at Surrounding Air Temperature of 0 to 55°C under I/O rated conditions) |
Output holding time | 20 ms min. (at Surrounding Air Temperature of 25°C under I/O rated conditions) |
Protection | Overcurrent protection | Activates when the current reaches 125% or more of the rated output current. Constant current voltage limiting. Automatic reset 7.9 A min. |
Overvoltage protection | Activates when the voltage reaches 26.4 V or more. Voltage turn-off. Operation resumes when the input power isturned on again.*2 |
Display | Display power | 3-digit, 7-segment LED (Character height: 10 mm) |
Power off memory time | Approx. 10 years (at 20°C) |
Display resolution | 0.1A/0.4V /1% |
Applicable standards | Safety standards | UL508, UL60950-1 CSA C22.2 No.14, CSA C22.2 No.60950-1 EN60950-1, EN50178 IEC60950-1 |
EMC standard | FCC Part15B Class A, EN55011 Class A, EN61000-6-2 |
Limits for harmonic current emissions | EN61000-3-2*3 |
Other | Parallel operation | Possible (OP-42207 is required.)*4 |
Series operation | Possible (External diode is required.)*4 |
Cooling method | Natural air-cooling |
Environmental resistance | Insulation resistance | 100 MΩ min. (with 500 VDC megohmmeter) (across input and output terminals) (across input terminals and PE terminal) |
Ambient temperature | -10 to +55 °C (No freezing) (See "Output conditions".) |
Storage temperature | -20 to +70 °C (No freezing) |
Relative humidity | 25 to 85 % RH (No condensation) |
Withstand voltage | 3.0 kVAC, 50/60 Hz, 1 min (across input and output terminals) 2.0 kVAC, 50/60 Hz, 1min (across input terminals and PE terminal) 500 VAC, 50/60 Hz, 1min (across output terminals and PE terminal) |
Vibration resistance | 10 to 57 Hz, Double amplitude 0.3 mm, 57 to 500 Hz, 19.6 m/s2 (2 G), 5.5-minute cycle, 2 hours in each of the X, Y, and Z directions |
Shock resistance | Peak acceleration: 300 m/s2, 2 times in each of the X, Y, and Z directions |
Weight | Approx. 700 g |
*1 The rated input voltage and rated frequency when applying for safety standards are 100 to 240 VAC, 50/60 Hz. *2 To return, turn OFF the input power supply and after leaving it off for 1 minute or more, plug in the input power supply again. The E/F Series is a Zener diode clamp type. It will not restart after the protection circuit operation. *3 For the MS2-H100, this is applicable only when the load ratio is 70% or lower. *4 The applicable standards do not apply for parallel and serial operations. |